EasyManua.ls Logo

MR tapcon 240 - Parallel operation

MR tapcon 240
174 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Functions and settings
Maschinenfabrik Reinhausen 2014104 222/08 ENTAPCON® 240
Circuit F
TAPCON® 240
Figure 64: Phase difference -30 3PH
The voltage transformer VT is connected to the outer conductors L1 and
L2.
The current transformer CT is looped into the outer conductor L1.
The current I
L1
lags behind U
L1
-U
L2
by 30°. This corresponds to a phase
shift of -30°.
The voltage drop on an outer conductor is determined by the current I
L1
.
To set the phase difference for the transformer circuit, proceed as follows:
1. > Configuration > Transformer data > Press until the
desired parameter is displayed.
ð Transformer circuit.
2. Press or to select the required phase difference.
3. Press .
ð The phase difference is set.
Parallel operation
In theParallel operation menu item, you can set the parameters needed for
parallel transformer operation. Parallel transformer operation is used to in-
crease the throughput capacity or short-circuit capacity in one place.
Compliance with the following general conditions is required for operating
transformers in parallel:
Identical rated voltages
Transformer power ratio (< 3 : 1)
Maximum deviation of short-circuit voltages (U
K
) for transformers con-
nected in parallel < 10%
Same number of switching groups
The same current-transformer connection has to be used for all devices
running in parallel
7.9
Conditions for parallel
operation

Table of Contents

Other manuals for MR tapcon 240

Related product manuals