7 Functions and settings
Maschinenfabrik Reinhausen 201494 222/08 ENTAPCON® 240
Also refer to
2 Setting delay time for error message [► 96]
2 Setting desired value for regulator 2 [► 94]
2 Setting undervoltage limit value V< for regulator 2 [► 94]
2 Setting overvoltage limit value V> for regulator 2 [► 95]
Setting desired value for regulator 2
You can use this parameter to set the desired value for the device to be
monitored.
You can use the key to change the display to the following units:
Volts (V) Kilovolts (kV)
This value relates to the secondary
voltage of the system's voltage
transformer.
This value relates to the primary
voltage of the system's voltage
transformer.
Table 17: Units available
If you want to change the display from V to kV, you have to set the trans-
former data of the device to be monitored.
To enter the desired value of the device to be monitored, proceed as follows:
1. > Parameter > Cross-monitoring.
ð V
des.
regulator 2.
2. Press to increase the value or to reduce it.
3. Press .
ð The desired value of the device to be monitored is set.
Setting undervoltage limit value V< for regulator 2
You can use this parameter to set the undervoltage limit value V< of the de-
vice to be monitored. You can set the undervoltage limit value V< as an ab-
solute value (V or kV).
Setting absolute value
You can use the key to change the display to the following units:
7.7.1
7.7.2