7 Functions and settings
Maschinenfabrik Reinhausen 2014128 222/08 ENTAPCON® 240
To move the sequence to a precise time, proceed as follows:
1. > Info > Press until the desired display appears.
ð Time plotter.
2. Press until the setting box for the retrace date is highlighted.
ð The setting box is now highlighted and the value can be changed.
3. Press to advance the date by one digit or to move it back one
digit.
ð The retrace date is set. The sequence for the specified day appears in
the display.
Communication interface CIC1 (optional)
The following section describes how to configure the communication inter-
face.
Selecting the communication port
You can use this parameter to select the communication port used for the
CIC card. You can select the following options:
RS232
RS485
Ethernet (optional)
Fiber-optic cable (optional)
You can only select one communication port. All remaining ports remain dis-
abled. It is not possible to use several communication ports at the same
time.
This display is only provided for the following interface protocols:
DNP3
IEC 60870-5-101
IEC 60870-5-103
MODBUS ASCII/RTU
ABB SPA
To select the communication port, proceed as follows:
7.14
7.14.1