EasyManua.ls Logo

MR tapcon 240 - Setting undervoltage monitoring V<

MR tapcon 240
174 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Functions and settings
Maschinenfabrik Reinhausen 2014 79222/08 EN TAPCON® 240
Parameter Function
Off The device uses the relative limit values [%] you have
entered
On The device uses the absolute limit values [V] you have
entered
Table 14: Selection between relative and absolute value
To activate/deactivate the absolute limit values, proceed as follows:
1. > Parameter > Limit values.
ð Absolute limit values.
2. Press for On setting or for Off setting.
3. Press .
ð The absolute limit value is activated/deactivated.
Setting undervoltage monitoring V<
You can use these parameters to set the limit values for an undervoltage.
Undervoltage monitoring prevents tap-change operations if there is a power
cut.
If the measured voltage U
actual
falls below the set limit value , the red
LED U< lights up . The switching pulses to the motor-drive unit are blocked
at the same time provided you have activated the blocking undervoltage U<
parameter. Once the set signaling delay time [ 81]
has passed, the
signaling relay activates. The Undervoltage U< message appears in the
display. The message is reset as soon as the measured voltage U
actual
again
exceeds the limit value for undervoltage
. If the measured voltage U
actual
falls below 30 V (for example when the transformer is switched off), the
Undervoltage message is also displayed. You can however suppress
[ 82] this message.
7.5.2
Behavior

Table of Contents

Other manuals for MR tapcon 240

Related product manuals