EasyManua.ls Logo

MR tapcon 240 - Setting the phase difference for the current transformer;voltage transformer

MR tapcon 240
174 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Functions and settings
Maschinenfabrik Reinhausen 2014 101222/08 EN TAPCON® 240
1. > Configuration > Transformer data > Press until the
desired parameter is displayed.
ð Current transformer connection.
2. Press or to select the required connection terminal.
3. Press .
ð The current transformer connection is set.
Setting the phase difference for the current transformer/voltage
transformer
You can use this parameter to set the phase difference of the current trans-
former and voltage transformer. You can set the common transformer cir-
cuits as follows:
Tap-change
operation
Setting Measurement
method
Phase differ-
ence
A 0 1PH 1 phase
B 0 3PHN 3 phase
C 0 3PH 3 phase
D 90 3PH 3 phase 90°
E 30 3PH 3 phase 30°
F -30 3PH 3 phase -30°
Table 22: Set values for transformer circuit
Note the following sample circuits to select the correct transformer circuit.
Circuit A: 1-phase measurement in 1-phase grid
TAPCON® 240
Figure 59: Phase difference 0 1PH
The voltage transformer VT is connected to the outer conductor and
neutral conductor.
The current transformer CT is looped into the outer conductor.
The voltage U
L1
and current I
L1
are in phase.
The voltage drop on an outer conductor is determined by the current I
L1
.
7.8.5

Table of Contents

Other manuals for MR tapcon 240

Related product manuals