7 Functions and settings
Maschinenfabrik Reinhausen 2014 57222/08 EN TAPCON® 240
The waiting time between 2 consecutive switching pulses corresponds to the
set delay time T1 or delay time T2 .
Figure 34: Switching pulse time in normal mode
1 Set delay time T1 or T2 2 Set switching pulse time (for
example 1.5 seconds)
If the motor-drive unit does not start with the factory setting (1.5 seconds),
you need to extend the raise switching pulse time / lower switching pulse
time.
If you set the raise switching pulse time or lower switching pulse time to
1.5 seconds, for example , the next earliest switching pulse occurs in rapid
return control mode 1.5 seconds after the previous switching pulse
ended.
Switching pulse for rapid
return control