NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
138 BU 0200 en-3118
60 =
R stator ident
Stator resistance determined by means of measurement (P220)
the rotor resistance determined by measurement ((P220) Function 2)
the stray inductance determined by measurement ((P220)
Function 2)
the inductance determined by measurement ((P220) Function 2)
65 =
Reserved
Pos: 29 6 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par amet er/ Par amet erau fli st ung (P 000 .. .)/P 000- P099 /Par amet er P002 – Display-F a kt or @ 0\mod_1327573818457_388.docx @ 7409 @ @ 1
P002
Display factor
(Display factor)
S
0.01 ... 999.99
{ 1.00 }
The selected operating value in parameter P001 >Select of display< is multiplied with the scaling
factor in P000 and displayed in >Operating parameter display<.
It is therefore possible to display system-specific operating such as e.g. the throughput quantity
Pos: 29 7 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par amet er/ Par amet erau fli st ung (P 000 .. .)/P 000- P099 /Par amet er P003 – S uper vis or-Code [SK 1x0E, SK 2xxE, SK 2xxE-FDS] @ 2\mod_1346931544673_388.docx @ 42130 @ @ 1
P003 Supervisor code
(Supervisor code)
0 ... 9999
{ 1 }
0 =
The supervisor parameters and groups P3xx/P6xx are not visible, otherwise all.
1 =
All parameters are visible, except groups P3xx and P6xx.
2 =
All parameters are visible, except group P6xx.
All parameters are visible.
4 =
... 9999, only parameters P001 and P003 are visible.
Information
Display via NORDCON
If parameterisation is carried out with the NORDCON software, the settings 4 ... 9999 the
settings are as for the 0 setting. Settings 1 and 2 behave like setting 3.