5.2.6 Additional parameters
Parameter
{factory setting}
Setting value / Description / Note Supervisor Parameter set
Pos: 47 2 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P5 00-P5 99/Par amet er P501 – Umricht ern am e @ 0\mod_1328091645446_388.docx @ 10904 @ @ 1
P501 [-01]
...
[-20]
Inverter name
(Inverter name)
A…Z
(char)
{ 0 }
Free input of a designation (name) for the device (max. 20 characters). With this, the frequency
inverter can be uniquely identified for setting with NORD CON software or within a network.
Pos: 47 3 /Anlei tung en/El ektr onik/FU und Star ter /5. Par a meter/ Par a meter auf list ung (P0 00 . ..) /P5 00- P599/ Para meter P5 02 – Wert Leitfunktion [SK 2xxE] @ 2\mod_1346932163539_388.docx @ 42984 @ @ 1
P502 [-01]
...
[-03]
Value master function
(Master function value)
S P
0 ... 57
{ all 0 }
Selection of up to 3 master values of a Master for output to a bus system (see P503). The
assignment of these master values to the slave is carried out via (P546). Definition of frequencies:
( Section 8.10 "Definition of setpoint and actual value processing (frequencies)")
[-01] = Master value 1 [-02] = Master value 2 [-03] = Master value 3
Selection of possible setting values for master values:
0 =
Off
17 =
Value analogue input 1
SK2x0E: Analogue input 1 (P400[-01]),
SK2x5E:
AIN1 of the first I/O extension
(SK xU4-IOE (P400 [-03]))
1 =
Actual frequency
18 =
Value analogue input 2
SK2x0E: Analogue input 2 (P400[-02]),
SK2x5E: AIN2 of the first I/O extension
(SK xU4-IOE (P400 [-04]))
2 =
Actual speed
19 =
Setpoint freq. Master value, "Setpoint
frequency master value"
3 =
Current
20 =
Setpoint freq. after ramp master value,
"Setpoint frequency from ramp master
value“
4 =
Torque current
21 =
Actual freq. without slip Master value
"Actual frequency without master value
slip"
5 =
Digital IO status
22 =
Speed encoder
6 =
... 7 reserved, Posicon BU0210
23 =
Master actual with slip
(SW V1.3 and above)
"Actual frequency with slip"
8 =
Setpoint frequency
24 =
Master value Actual freq. w. slip
(SW
V1.3 and above)
"Actual frequency master value with slip"
9 =
Error number
53 =
Actual value 1 PLC
10 =
... 11 reserved, Posicon BU0210
54 =
Actual value 2 PLC
12 =
Bus IO Out Bits 0-7
55 =
Actual value 3 PLC
13 =
... 16 reserved, Posicon BU0210
56 =
Actual value 4 PLC
57 =
Actual value 5 PLC
NOTE: Details with regard to target and actual value processing: ( Section 8.9 "
target values").