NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
240 BU 0200 en-3118
Pos: 70 9 /Anlei tung en/El ektr onik/FU und Star ter/7 . Tec hnisch e D aten/ El ektr isc he D ate n [S K 1xxE , SK 2xx E, S K x xxE-F DS]/ Elekt risch e Date n 1~ 115V [S K 2xxE] @ 20\mod_1513683452174_388.docx @ 2376257 @ 3 @ 1
7.2.1 Electrical data 1~115 V
Device type SK 2x5E…
-250-112- -370-112- -550-112- -750-112-
Size
1 1 2 2
Nominal motor power
(4-pole standard motor)
230 V
0.25 kW
0.37 kW
0.55 kW
0.75 kW
240 V
1
/
3
hp
½ hp
¾ hp
1 hp
Mains voltage
115 V
1 AC 100 … 120 V,
±
10 %, 47 … 63 Hz
Input current
rms
1)
8.9 A 11.0 A 13.1 A 20.1 A
FLA
2)
8.9 A 10.8 A 13.1 A 20.1 A
Output voltage
230 V
3 AC 0 … 2 times mains voltage
Output current
3)
rms
1)
1.7 A
2.2 A
3.0 A
4.0 A
FLA motor mounting
2)
1.7 A
1.7 A
3.0 A
3.0 A
FLA wall mounting
2)
1.7 A
2.1 A
3.0 A
4.0 A
Min. brake resistance
Accessories
75
Ω
75
Ω
75
Ω
75
Ω
Motor-mounted (ventilated)
Max. continuous power / max. continuous current
S1-50°C
S1-40°C
S1-30°C
0.25 kW / 1.6 A
0.25 kW / 1.7 A
0.25 kW / 1.7 A
0.25 kW / 1.6 A
0.25 kW / 1.8 A
0.37 kW / 2.0 A
0.37 kW / 2.6 A
0.55 kW / 3.0 A
0.55 kW / 3.0 A
0.37 kW / 2.6 A
0.55 kW / 3.0 A
0.55 kW / 3.4 A
Max. permissible ambient temp. with nominal output current
S1
S3 70 % ED 10 min
S6 70 % ED 10 min (100 % / 20 % Mn)
47°C
50°C
50°C
23°C
35°C
30°C
40°C
50°C
45°C
11°C
25°C
20°C
Wall mounting (ventilated / unventilated)
Max. continuous power / max. continuous current
S1-50°C
S1-40°C
S1-30°C
0.25 kW / 1.6 A
0.25 kW / 1.7 A
0.25 kW / 1.7 A
0.25 kW / 1.6 A
0.37 kW / 2.0 A
0.37 kW / 2.1 A
0.55 kW / 3.0 A
0.55 kW / 3.0 A
0.55 kW / 3.0 A
0.55 kW / 3.0 A
0.55 kW / 3.3 A
0.55 kW / 3.6 A
Max. permissible ambient temp. with nominal output current
S1
S3 70 % ED 10 min
S6 70 % ED 10 min (100 % / 20 % Mn)
48°C
50°C
50°C
36°C
40°C
40°C
50°C
50°C
50°C
16°C
30°C
25°C
General fuses (AC) (recommended)
slow-blowing
16 A
16 A
16 A
25 A
Isc
4)
[A]
UL fuses (AC) – permitted
Class
10 000
65 000
100 000
Fuse
5)
RK5
(x)
x
30 A
30 A
30 A
30 A
CC, J, R, T, G, L
(x)
x
30 A
30 A
30 A
30 A
Bussmann FRS-
(x)
x
R-30
R-30
R-30
R-30
CB
6)
(≥ 115 V)
x
25 A 25 A 25 A 25 A
1) Note derating curve (

Section 8.4.4 "Reduced output current due to mains voltage").
2) FLA – Full Load Current, maximum current for the entire mains voltage range as stated above (100 V – 120 V) according to UL/CSA
3) FLA (S1-40°C), FLA motor mounting: relates to a motor with fans
4) Maximum permissible mains short circuit current
5) The use of an SK TU4-MSW(-…) module, limits the permissible short-circuit in the mains to 10 kA
6) "inverse time trip type" in acc. with UL 489
Pos: 71 0 /Allg emein/ Allg emeing ültig e Mod ule/---------Sei tenumbr uch ko mpakt --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1

Table of Contents

Other manuals for Nord Drivesystems NORDAC FLEX SK 210E Series

Questions and Answers: