5.2.8 Information
Parameter Setting value / Description / Note Supervisor Parameter set
Pos: 55 5 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P7 00-P7 99/Par amet er P700 – Aktuel ler Betr iebsz usta nd @ 0\mod_1328170483810_388.docx @ 12318 @ @ 1
P700 [-01]
...
[-03]
Actual operating status
(Actual operating status)
0.0 ... 25.4
Display of current messages for the present operating status of the frequency inverter such as
faults, warnings or the reason why switch-on is disabled (please see chapter 6 "Operating status
messages").
[-01] = Present fault, shows the currently active (unacknowledged) fault (please see section
"Error messages").
[-02] = Present warning, indicates a current warning message (please see section "Warning
messages").
[-03] = Reason for disabled starting, indicates the reason for an active start disable (please see
section "Switch-on block messages").
NOTE
SimpleBox / ControlBox: the error numbers of the warning messages and faults can be displayed
using SimpleBox and ControlBox.
ParameterBox: with the ParameterBox the messages are displayed in plain text.. In addition, the
reason for a possible disabling of starting can also be displayed.
Bus: The display of bus-
level error messages is displayed in decimal integer format. The
displayed value must be divided by 10 in order to correspond with the correct format.
Example: Display: 20 → Error number: 2.0
Pos: 55 6 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P7 00-P7 99/Par amet er P701 – Letzte Stör ung 1.. .5 @ 0\ mod_1328170536746_388.docx @ 12341 @ @ 1
P701 [-01]
...
[-05]
Last fault 1 ... 5
(Last fault 1...5)
0.0 ... 25.4 This parameter stores the last 5 faults
(please see chapter
0 "Error messages").
The SimpleBox / ControlBox must be used to select the corresponding memory location 1...5-
(Array parameter), and confirmed using the OK / ENTER key to read the stored error code.
Pos: 55 7 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P7 00-P7 99/Par amet er P702 – Freque nz letzt e Stör ung 1.. .5 @ 0\mod_1328170589463_388.docx @ 12364 @ @ 1
P702 [-01]
...
[-05]
Last frequency error
(Last frequency error 1...5)
S
-400.0 ... 400.0 Hz This parameter stores the output frequency that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
The SimpleBox / ControlBox must be used to select the corresponding memory location 1...5-
(Array parameter), and confirmed using the OK- / ENTER key to read the stored error code.