5 Parameter
BU 0200 en-3118 145
Pos: 32 4 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P1 00-P1 99/Par amet er P113 – Tippfr equ enz [SK 2x xE] @ 2\mod_1346931600084_388.docx @ 42205 @ @ 1
P113
Jog frequency
(Jog frequency)
S P
-400.0 ... 400.0 Hz
{ 0.0 }
When using the SimpleBox or ParameterBox
to control the FI, the jog frequency is the initial
value following successful enabling.
Alternatively, when control is via the control terminals, the jog frequency can be activated via one
of the digital inputs.
The setting of the jog frequency can be done directly via this parameter or, if the FI is enabled via
the keyboard, by pressing the OK key. In this case, the actual output frequency is set in
parameter P113 and is then available for the next start.
NOTE: Specified setpoints via the control terminals, e.g. jog frequency, fixed frequencies or
analogue setpoints, are generally added with the correct sign. The set maximum frequency
(P105) cannot be exceeded and the minimum frequency (P104) cannot be undershot.
Pos: 32 5 /Anlei tung en/El ektr onik/FU und St art er/5 . P ara meter /P ara meter au fli stung (P 000 .. .)/P 100- P199 /Para meter P114 – L üftzei t B re ms e @ 0 \mod_1327587947470_388.docx @ 7815 @ @ 1
P114
Brake delay off
(Brake release time)
S P
0 ... 2.50 s
{ 0.00 }
Electromagnetic brakes have a delayed reaction time during ventilation, which depends on
physical factors. This can lead to the motor running while the brake is still applied, which will
cause the inverter to switch off with an overcurrent report.
This release time can be taken into account in parameter P114 (Brake control).
During the adjustable ventilation time, the FI supplies the set absolute minimum frequency (P505)
thus preventing movement against the brake.
See also the parameter >Brake reaction time< P107 (setting example).
NOTE:
If the brake ventilation time is set to "0", then P107 is the brake ventilation and reaction time.
Pos: 32 6 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 ...) /P100- P199 /Para meter P120 – O pti onsü ber wac hung [SK 1 x0E, SK 2xxE , S K 54 xE, SK 2xx E-FDS ] @ 2 \mod_1346931600646_388.docx @ 42230 @ @ 1
P120 [-
[-
Option monitoring
(Option monitoring)
S
0 ... 2
{ 1 }
Monitoring of communication at system bus level (in case of error: error message 10.9)
Array levels:
[-01] = Extension 1 (BUS unit)
[-02] = Extension 2 (second I/O unit)
[-03] = Extension 3 (first I/O unit)
[-04] = Extension 4 (reserved)
Setting values
0 = Monitoring OFF
1 =
Auto
, communication is only monitored if an existing communication is interrupted. If a
module which was previously present is not found after switching on the mains, this does
not result in an error
Monitoring only becomes active when an extension starts communication with the FI.
2 =
Monitoring active immediately "Monitoring active immediately" ,
the corresponding module immediately after the mains are switched on.
not detected on switch-on, the FI remains in the status "not ready for switch-
seconds and then triggers an error message.
Note: If error messages which are detected by the optional module (e.g. errors at field bus level)
are not to result in a shut-do
wn of the drive electronics, parameter (P513) must also be set to the
value {-0,1}.