NORDAC FLEX (SK 200E ... SK 235E)Users Manual for Frequency Inverters
190 BU 0200 en-3118
Pos: 48 2 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P5 00-P5 99/Par amet er P509 Quell e Steuer wort [SK 1x0E , SK 2xxE] @ 2\mod_1346932164693_388.docx @ 43032 @ @ 1
P509
Control word source
(Control word source)
S
0 ... 4
{ 0 }
Selection of the interface via which the FI is controlled.
0 =
Control terminals or keyb. cont., "Control terminals or keyboard control" ** with the
SimpleBox (if P510=0), the ParameterBox or via BUS I/O bits.
1 =
Only control terminals *, the FI can only be controlled via the digital and analogue inputs
or via the bus I/O Bits.
2 =
USS *
, the control signals (enable, rotation direction, etc.) are transferred via the RS485
interface, and the setpoint is transferred via the analogue input or the fixed frequencies.
3 =
System bus *, setting for actuation by master via a bus interface
4 =
System bus broadcast *, setting for actuation by a master drive in Master / Slave mode
(e.g. with synchronous applications)
*) Keyboard
control (SimpleBox, ParameterBox) is disabled, parameterisation is still
possible.
**) If communication is interrupted during keyboard control (timeout 0.5 sec), the FI will
block without an error message.
NOTE:
For details of the optional bus systems, please refer to the relevant supplementary bus manuals.
- www.nord.com
Pos: 48 3 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P5 00-P5 99/Par amet er P509 Quell e Steuer wort - Ergänzung [SK 2xxE] @ 9\mod_1448293499605_388.docx @ 265981 @ @ 1
As an alternative to setting the parameter, System Bus
can also be selected with DIP switch
S1:3.
Pos: 48 4 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 ...) /P500- P599 /Para meter P510 Q uelle Sol lwer te [SK 1 x0E, SK 2 xxE] @ 2\mod_1346932165333_388.docx @ 43056 @ @ 1
P510 [-01]
[-02]
Setpoints source
(Setpoints source)
S
0 ... 4
{ [-01] = 0 }
{ [-02] = 0 }
Selection of the setpoint source to be parameterised.
[-01] = Main setpoint source [-02] = Subsidiary setpoint source
Selection of the interface via which the FI receives the setpoint.
0 =
Auto: The source of the setpoint is
automatically derived from the setting of
parameter P509.
2 =
USS, see P509
3 =
System bus, see P509
1 =
Only control terminals, digital and
analogue inputs control the frequency,
including fixed frequencies
4 =
System bus broadcast, see P509
Pos: 48 5 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P5 00-P5 99/Par amet er P511 USS-Baudrate [SK 1x0E, SK 2xxE, SK 2xx-FD S] @ 2\mod_1346932165972_388.docx @ 43080 @ @ 1
P511
USS baud rate
(USS baud rate)
S
0 ... 3
{ 3 }
Setting of the transfer rate (transfer speed) via the RS485 interface. All bus participants must
have the same baud rate setting.
0 =
4800 Baud
2 =
19200 Baud
1 =
9600 Baud
3 =
38400 Baud