5 Parameter
BU 0200 en-3118 203
Pos: 53 5 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P5 00-P5 99/Par amet er P550 EEPROM Ko pierau ftrag [SK 2xxE] @ 2\mod_1346932173382_388.docx @ 43368 @ @ 1
P550
EEPROM copy order
(EEPROM copy order)
0 ... 3
{ 0 }
The frequency inverter is equipped with an internal EEPROM and a plug-
in EEPROM ("Memory
Module") which operates in parallel to this for the storage and management of parameter data.
The data from the
device are managed in parallel on both devices, so that a safe and rapid
exchange of parameter settings in the device is possible for commissioning or in case of service.
The data sets saved in the internal EEPROM and in the Memory Module can be copied between
the devices. This includes a PLC program that is present on the device.
0 =
No change
2 =
Internal → External, the data set is
copied from the internal EEPROM to
the memory module (external
EEPROM)
1 =
External → Internal, the data set is
copied from the memory module
(external EEPROM) to the internal
EEPROM
3 =
External < - > Internal, the data sets
are exchanged between the two
EEPROMs
Note:
Since software version 1.4 R2, the frequency converter always uses the data record
that is stored on the internal EEPROM.
With older versions the data record for the external EEPROM (memory module) is
used. The parametrisation of the internal EEPROM was only used if no Memory
Module was plugged in.
Pos: 53 6 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P5 00-P5 99/Par amet er P552 CAN Master Zyklus zeit [SK 1 x0E, SK 2 xxE, SK 2 xxE-FDS] @ 2\ mod_1346933835351_388.docx @ 43776 @ @ 1
P552 [-01]
[-02]
CAN Master cycle
(CAN Master cycle time)
S
0.0 / 0.1 … 100.0 ms
{ all 0.0 }
In this parameter, the cycle time for the system bus master mode and the CAN open encoder is
set (see P503/514/515):
[01] = CAN Master function, Cycle time for system bus master functions
[02] = CANopen Abs. encoder, "CANopen absolute encoder", system bus cycle time of absolute
encoder
With the setting 0 = "Auto" the default value (see table) is used.
According to the Baud rate set, there are different minimum values for the actual cycle time:
Baud rate Minimum value t
Z
Default CAN Master Default CANopen Abs.
10kBaud
10ms
50ms
20ms
20kBaud
10ms
25ms
20ms
50kBaud
5ms
10ms
10ms
100kBaud
2ms
5ms
5ms
125kBaud
2ms
5ms
5ms
250kBaud
1ms
5ms
2ms
500kBaud
1ms
5ms
2ms
1000kBaud:
1ms
5ms
2ms
Pos: 53 7 /Allg emein/ Allg emeing ültig e Mod ule/---------Sei tenumbr uch ko mpakt --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1