E005
5.0 Overvoltage UZW
Link circuit voltage too high
• Increase deceleration time (P103)
• If necessary, set switch-off mode (P108) with delay
(not with lifting equipment)
• Extend emergency stop time (P426)
• Fluctuating speed (e.g. due to high centrifugal
masses) ïƒ adjust U/f characteristic curve if
necessary (P211, P212)
Devices with brake chopper:
• Reduce energy return using a braking resistor
• Check the function of the connected braking resistor
(broken cable)
• Resistance value of connected braking resistor too
high
5.1 Mains overvoltage
Mains voltage is too high
• See technical data ( Section 7)
Pos: 651 /A nleit ung en/El e ktr onik /FU und Star ter /6. M eldung en zu m B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ Fehl er E0 06 [ SK 5 xxE, SK 2xxE, SK 2 xxE-FD S] @ 2\mod_1361458416246_388.docx @ 58807 @ @ 1
E006
6.0 Charging error
Link circuit voltage is too low
• Mains voltage too low
• See technical data ( Section
7)
6.1 Mains undervoltage
Mains voltage too low
• See technical data ( Section 7)
Pos: 65 2 /Anlei tu nge n/El ektr oni k/FU un d St art er/6 . M eld ung en z um B etr iebs zus ta nd/S tör mel dung en (Auf list ung )/F ehl er E 007 [SK 135 E, SK 200E , SK 500E, S K xxx E-FD S] @ 2\mod_1361460459184_388.docx @ 58907 @ @ 1
E007
7.0 Mains phase error
Error at terminal connection side
• a network phase is not connected
• network is non-symmetrical
Pos: 653 /A nleit ung en/El e ktr onik /FU und Star ter /6. M eldung en zu m B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ Fehl er E0 08 [ SK 2 xxE] @ 2\mod_1347453314366_388.docx @ 46576 @ @ 1
E008
8.0 Parameter loss
(maximum EEPROM value
exceeded)
Error in EEPROM data
• Software version of the stored data set not
compatible with the software version of the FI.
NOTE: Faulty parameters are automatically reloaded
(default data).
• EMC interferences (see also E020)
8.1 Inverter type incorrect
• EEPROM faulty
8.2 Reserved
8.3 EEPROM KSE error
(Customer interface incorrectly
identified (customer’s interface
equipment))
The upgrade level of the frequency inverter was not
correctly identified.
EEPROM with a firmware status of version 1.2 or above
plugged in to an FI with older firmware status → Loss of
parameters! (see also Information in section
5 )
• Switch mains voltage off and on again.
8.4 Internal EEPROM error
(Database version incorrect)
8.7 EEPR copy not the same
Pos: 65 4 /Anlei tung en/El ektr onik/FU und Star ter/6 . Meld ungen zum Betr iebsz usta nd/Stör mel dung en (Aufli st ung)/ Fehl er E0 09 "r es ervi ert" [S K 1 80E/ SK 2 xxE/ S K2xx E-FD S] @ 2\mod_1347453797027_388.docx @ 46701 @ @ 1
E009
--- Reserved