Operating Parameters
B-3
P/N 7135268B
E 2008 Nordson Corporation
PURBlue EC
3 Change History Log (Non-editable)
Description:
Records the last ten changes made to either the setpoint temperatures or the
operating parameters.
Value:
Resolution:
Default:
P-_ (unused log entry)
Format:
Refer to section Operation, Structure of Change History Log.
Use:
Use the right display scroll key to review the last ten changes made to either
the setpoint temperatures or the operating parameters. Empty log entries are
indicated by ”P-_”
4 Ready Delay Time
Description:
The amount of time that will elapse after all of the components have reached
their setpoint temperatures before the Ready LED turns on. The ready delay
time only functions when the temperature of the tank, at the time the melter is
turned on, is more than 27 °C (50 °F) or more below its setpoint temperature.
The ready delay time begins when all components are within 3 °C (5 °F) of their
respective setpoint temperature.
Value:
0 to 60 minutes
Resolution:
1 minute
Default:
0 minutes
Format:
Use:
The ready delay allows the tank additional time to heat up before the pump
starts up.
NOTE: The time remaining on the ready delay is indicated in minutes in the
right display at the end of every automatic scan cycle. Below one minute, the
time remaining appears in seconds.
Pressing the Heater key twice overrides the ready delay time. BUT
CAUTION: Always allow at least a 30 minute ready delay to prevent the pump
from being damaged when it is switched on.
Original state: 30 min
5 Service Interval
Description:
The number of hours of heater operation that must elapse before the Service
required LED lights up.
Value:
0 hours (disabled) to 8736 hours (one year)
Resolution:
1 hour
Default:
500 hours
Format:
Use:
Set the service interval time to signal a user-defined maintenance event, such
as changing the filter. The Service required LED lights up after the preset time
has elapsed.
Press the Clear/Reset key to turn off the service LED and reset the time when
the melter is in Normal mode.
Note: Heater hours of operation are counted whenever the heater LED is on.