Operating Parameters
B-17
P/N 7135268B
E 2008 Nordson Corporation
PURBlue EC
Seven-day Clock (contd.)
50 Current Day
Description:
Used to set the current day of the week.
Value:
1 to 7 (1 = Monday, 2 = Tuesday, etc.)
Resolution:
1
Default:
—
Format:
—
Use:
—
51 Current Time
Description:
Used to set the current time of day.
Value:
0000 to 2359 (European time format)
Resolution:
1 minute
Default:
(Time set at factory)
Format:
Hour, Hour: Minute, Minute
Use:
This setting only needs to be made once for all daily schedules.
55 Schedule 1 Heaters On
Description:
Used to set the time that the clock turns on the heaters during schedule 1.
Value:
0000 to 2359, - - - -
Resolution:
1 minute
Default:
0600
Format:
Hour, Hour: Minute, Minute
Use:
Set the desired time for the heaters to turn on.
To disable this parameter, set the parameter’s value to ”- - - -” by
simultaneously pressing both of the right display scroll keys.
56 Schedule 1 Heaters Off
Description:
Used to set the time that the clock turns off the heaters during schedule 1.
Value:
0000 to 2359, - - - -
Resolution:
1 minute
Default:
1700
Format:
Hour, Hour: Minute, Minute
Use:
To disable this parameter, set the parameter’s value to ”- - - -” by
simultaneously pressing both of the right display scroll keys.