Connecting commercial power 3-17
AccessNode Series 800A Outside Plant Cabinet Installation 323-3001-210 Issue 1.0
Procedure 3-5
Wiring the ac power pedestal
Use this procedure to wire the ac power pedestal option.
Wire the ac power pedestal for S800A cabinet installed with the power
pedestal option.
Tools required
voltmeter
one medium flat blade screwdriver
one small flat blade screwdriver
one wire stripper for 6 AWG, 10 AWG and 12 AWG wire
Material required
one 2-inch NPT knockout connector or equivalent
Precautions
The following safety precautions should be observed at all times during the
cabinet installation procedures:
Do not open the front or rear doors unless the cabinet is firmly secured to
the mounting pad as described in Chapter 2, “Installing the cabinet”.
Observe all NEC and local codes for electrical wiring.
—continued—
CAUTION 1
Electrical shock hazard
The procedures listed in this chart should be done by a
qualified electrician. The procedures outlined are
recommended guidelines; be sure to follow all local codes
for wiring procedures.
CAUTION 2
Fire hazard
Remove all paper and any other combustible materials from
inside the cabinet before the cabinet is powered up.
Failure to comply with this warning could result in a fire.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nortel SONET AccessNode 800A Series and is the answer not in the manual?

Nortel SONET AccessNode 800A Series Specifications

General IconGeneral
BrandNortel
ModelSONET AccessNode 800A Series
CategoryNetwork Hardware
LanguageEnglish

Related product manuals