CT Analyzer User Manual
182 OMICRON
819.xxx Warning [819.xxx] File name contains an invalid character.
Reason: An invalid character was used to specify the file name.
Invalid characters: \ / : * ? \ < > |
Solution: Only use valid characters for the file name.
820.xxx Error [820.xxx] Memory management error. Contact the next OMICRON service center.
Reason: Memory management error.
Solution: Switch the CT Analyzer off, wait a second then switch it on again. If this error occurs more
frequently, you should contact your next OMICRON service center.
821.xxx Error [821.xxx] Could not update firmware.
Reason: An error has occurred in the boot loader software.
Solution: Insert a Compact Flash card with valid software (CTAnalyzer.bin) in the directory
A:\Omicron\ and switch the CT Analyzer off and on again.
823.xxx Error [823.xxx] Could not update user text!
Reason: An error has occurred in the user text loader software.
Solution: Insert a Compact Flash card with valid software (CTUser_xxx.bin) in the directory
A:\Omicron\ and try again.
824.xxx Error [824.xxx] An internal software error has occurred at address xxxxxxxH. To log this error,
make sure that a CF card is inserted and then press OK. Please send the file \OMICRON\
ErrorLog.xml on the CF card to the next OMICRON service center.
Reason: Invalid result in a floating point operation (NaN).
Solution: Contact your next OMICRON service center.
825.xxx Warning [825.xxx] Size of file [FileName] >= 1Mbyte.
Reason: The size of the file copied to the CT Analyzer Compact Flash card or virtual disc is > 1 MB.
Solution: Avoid transfer of large files > 1 MB to the CT Analyzer.
826.xxx Error [826.xxx] The CT standard of the loaded report is not supported by the current firmware
version. Please check for a CT Analyzer firmware update.
Reason: You are trying to load a report that makes use of a CT standard your current firmware
version of CT Analyzer does not support.
Solution: Perform a firmware update to the latest version for your CT Analyzer.
830.xxx License < ... > is invalid.
Reason: An invalid license entry was found in the license file Omicron.lic on the CF Card.
Solution: Specify a valid license key.
831.xxx Setting value for < ... > is invalid. The default value of < ... > is used.
Reason: Invalid item in file Settings.inf.
Solution: The file Settings.inf in the Omicron directory on the CF card of the CT Analyzer has a
formatting error in one of the parameters. Delete this file and check the settings in the menu
Main Menu -> Settings -> Misc. Settings. If necessary, change the settings and store the
file again.
832.xxx Lifetime of relays near end. Contact the next OMICRON service center soon to arrange a hardware
service.
Reason: The relays inside the CT Analyzer near the end of their lifetime (more than 1,000,000
measurements performed).
Solution: Arrange a hardware service in order to replace the relays.
833.xxx You are about to load a report with an invalid hash code. Some measurement values may not be
authentic.
Reason: The file checksum is not valid.
Solution: Check the authenticity of the report file loaded.
834.xxx No valid license was found in this file!
Reason: No valid license found.
Solution: Check the license file. The license possibly does not correspond to the serial number of
the CT Analyzer.