OMICRON 181
Error and warning messages
806.xxx Warning [806.xxx] Flash card access error. Corrupt directory structure.
Reason: The file system sent an error message.
Solution: Try to backup the data on the Compact Flash card to a PC and perform formatting of the
Compact Flash card.
807.xxx Warning [807.xxx] Nothing to paste.
Reason: No file(s) selected to paste.
Solution: Select one or more files using the Copy or Cut function and try again.
808.xxx Warning [808.xxx] Renaming of folders not supported.
Reason: This action is not supported.
Solution: Renaming of folders is not supported by the CT Analyzer.
809.xxx Warning [809.xxx] Are you sure you want to format the CF card? All data will be lost!
Reason: This warning always appears before formatting of a Compact Flash card is executed, since
all data stored on the Compact Flash card will be erased during formatting.
Solution: Press Format to start formatting or Abort to cancel the operation without formatting the
Compact Flash card.
810.xxx Warning [810.xxx] File exists. Do you want to overwrite it?
Reason: The file name used to save the data already exists. This warning always appears before
overwriting files on the Compact Flash card.
Solution: Enter another file name, if desired.
811.xxx Warning [811.xxx] Are you sure you want to delete <File Name>?
Reason: This warning always appears prior to the deletion of a file on the Compact Flash card.
Solution: Press Yes to delete the file or No to return to the file system card without deleting the file.
812.xxx Warning [812.xxx] Are you sure you want to delete all selected files?
Reason: This warning always appears prior to the deletion of files on the Compact Flash card.
Solution: Press Yes to delete the files or No to return to the file system card without deleting the files.
813.xxx Warning [813.xxx] One or more parameters could not be found. Some calculations may not work.
Reason: The .xml report file read from the Compact Flash card is of a newer format than the device
can generate.
Solution: The loaded file is incompatible or the software version on your CT Analyzer is older than
the software version that has generated the report. To enable your CT Analyzer to read this
report, it is necessary to update the CT Analyzer software.
814.xxx Warning [814.xxx] You tried to load an old report. One or more parameters could not be found.
Some calculations may not work.
Reason: One or more entries could not be found in the .xml report file.
Solution: The software version on the CT Analyzer is newer than the software version used to
generate the report. The report probably does not contain all parameters supported by the
new CT Analyzer software.
815.xxx Error [815.xxx] Folder must be empty. Can't remove folder <Folder Name>.
Reason: The folder selected for deletion is not empty. Only empty folders can be deleted.
Solution: Navigate to the folder you want to delete. Open the folder and delete all contained files and
subfolders. Then you can delete the empty folder.
816.xxx Error [816.xxx] You tried to load a report built with a <Device>.
Reason: The .xml file seems to be not a CT Analyzer report.
Solution: The report cannot be loaded by the CT Analyzer.
817.xxx Error [817.xxx] The xml file has no valid OMICRON report style.
Reason: The .xml file has no valid OMICRON report style.
Solution: The report cannot be loaded by the CT Analyzer.
818.xxx Warning [818.xxx] Moving of folders not supported.
Reason: Moving of folders is not supported by the CT Analyzer.
Solution: Select only files to move, not folders. Using the shift key and the up/down cursor keys it is
possible to select any number of files within a folder.