EasyManua.ls Logo

Omron CP1E Series - Page 189

Omron CP1E Series
260 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9-29
9 Using Expansion Units and Expansion I/O Units
CP1E CPU Unit Hardware User’s Manual(W479)
9-3 Analog I/O Units
9
9-3-4 Flow of Processing
2
Wire to analog I/O devices.
(1) Wiring internal circuits of the CPU Unit
(2) Wiring analog output devices to the Analog I/O Unit
(3) Wiring analog input devices to the Analog I/O Unit
Precautions for Correct UsePrecautions for Correct Use
Do not connect the shield when using shielded twisted-pair cables.
When an input is not being used, short the + and - terminals.
Separate wiring from power lines (AC power supply lines, high-voltage lines, etc.)
When there is noise in the power supply line, install a noise filter on the input section and the
power supply terminals.
Analog Inputs Analog Outputs
Analog ground
Input 0
Input 1
Analog ground
Output
Internal circuits
510 k
510 k
510 k
510 k
250
250
COM0 ()
V IN0
V IN1
COM1 ()
Internal circuits
COM ()
V OUT
I OUT
AG
NC
NC
I IN0
I IN1
V IN
COM
I IN
V IN
COM
I IN
Analog
device
with
voltage
output
+
+
Analog
I/O Unit
Analog
device
with
current
output
Analog
I/O Unit
2-core shielded
twisted-pair cable
FG
2-core shielded
twisted-pair cable
FG
FG
FG
V OUT
COM
I OUT
V OUT
COM
I OUT
Analog
device
with
voltage
input
+
+
Analog
I/O Unit
Analog
device
with
current
input
Analog
I/O Unit
2-core shielded
twisted-pair cable
2-core shielded
twisted-pair cable

Table of Contents