Variable Area Map Section 5-10
Variable
type
Address ch Setting data name Description
C1 0000 - Operation/adjustment
protection
00000000H (0): No restriction at the operation/adjustment lev-
els
00000001H (1): Moving to adjustment level is disabled.
00000002H (2): Only “PV” and “PV/SP” display and change
enabled.
00000003H (3): Only “PV” and “PV/SP” display enabled.
0001 Initial setting/communica-
tions protection
00000000H (0): Moving to initial level/communications setting
level enabled and moving to advanced func-
tion setting level displayed.
00000001H (1): Moving to initial level/communications setting
level enabled and moving to advanced func-
tion setting level not displayed.
00000002H (2): Moving to initial setting/communications set-
ting levels is disabled.
0002 Setting change protection 00000000H (0): OFF (Setting changes using the E5ZN-SDL
enabled.)
00000001H (1): ON (Setting changes using the E5ZN-SDL dis-
abled.)
0003 1 SP Lower limit of SP to upper limit of SP
0004 Alarm value 1 FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
0005 Alarm upper limit value 1 FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
0006 Alarm lower limit value 1 FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
0007 Alarm value 2 FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
0008 Alarm upper limit value 2 FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
0009 Alarm lower limit value 2 FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
000A Alarm value 3 FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
000B Manual manipulated
value
Standard: FFFFFFCEH to 0000041AH (−5.0 to 105.0)
Heating/cooling: FFFFFBE6H to 0000041AH (−105.0 to 105.0)
000C Heater burnout detection 00000000H to 000001F4H (0.0 to 50.0) (See note 1.)
000D SP 0 Lower limit of SP to upper limit of SP
000E SP 1 Lower limit of SP to upper limit of SP
000F Temperature input offset
value
FFFFF831H to 0000270FH (−199.9 to 999.9)
0010 Upper limit temperature
input offset value
FFFFF831H to 0000270FH (−199.9 to 999.9)
0011 Lower limit temperature
input offset value
FFFFF831H to 0000270FH (−199.9 to 999.9)
0012 Proportional band 00000001H to 0000270FH (0.1 to 999.9)
0013 Integral time 00000000H to 00000F9FH (0 to 3999)
0014 Derivative time 00000000H to 00000F9FH (0 to 3999)
0015 Cooling coefficient 00000001H to 0000270FH (0.01 to 99.99)
0016 Dead band FFFFF831H to 0000270FH (−199.9 to 999.9)
0017 Manual reset value 00000000H to 000003E8H (0.0 to 100.0)
0018 Heating hysteresis 00000000H to 0000270FH (0.1 to 999.9)
0019 Cooling hysteresis 00000000H to 0000270FH (0.1 to 999.9)