93
Variable Area Map Section 5-10
C1 0100 - Operation/adjustment
protection
00000000H (0): No restriction at the operation/adjustment lev-
els
00000001H (1): Moving to adjustment level is disabled.
00000002H (2): Only “PV” and “PV/SP” display and change
enabled.
00000003H (3): Only “PV” and “PV/SP” display enabled.
0101 Initial setting/communica-
tions protection
00000000H (0): Moving to initial level/communications setting
level enabled and moving to advanced func-
tion setting level displayed.
00000001H (1): Moving to initial level/communications setting
level enabled and moving to advanced func-
tion setting level not displayed.
00000002H (2): Moving to initial setting/communication setting
levels is disabled.
0102 Setting change protection 00000000H (0): OFF (Setting changes using E5ZN-SDL
enabled.)
00000001H (1): ON (Setting changes using E5ZN-SDL dis-
abled.)
0103 2 SP Lower limit of SP to upper limit of SP
0104 Alarm value 1 FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
0105 Upper limit alarm value 1 FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
0106 Lower limit alarm value 1 FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
0107 Alarm value 2 FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
0108 Upper limit alarm value 2 FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
0109 Lower limit alarm value 2 FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
010A Alarm value 3 FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
010B Manual manipulated vari-
able
Standard: FFFFFFCEH to 0000041AH (5.0 to 105.0)
Heating/cooling: FFFFFBE6H to 0000041AH (105.0 to 105.0)
010C Heater burnout detection 00000000H to 000001F4H (0.0 to 50.0) (See note 1.)
010D SP 0 Lower limit of SP to upper limit of SP
010E SP 1 Lower limit of SP to upper limit of SP
010F Temperature input offset
value
FFFFF831H to 0000270FH (199.9 to 999.9)
0110 Upper limit temperature
input offset value
FFFFF831H to 0000270FH (199.9 to 999.9)
0111 Lower limit temperature
input offset value
FFFFF831H to 0000270FH (199.9 to 999.9)
0112 Proportional band 00000001H to 0000270FH (0.1 to 999.9)
0113 Integral time 00000000H to 00000F9FH (0 to 3999)
0114 Derivative time 00000000H to 00000F9FH (0 to 3999)
0115 Cooling coefficient 00000001H to 0000270FH (0.01 to 99.99)
0116 Dead band FFFFF831H to 0000270FH (199.9 to 999.9)
0117 Manual reset value 00000000H to 000003E8H (0.0 to 100.0)
0118 Heating hysteresis 00000001H to 0000270FH (0.1 to 999.9)
0119 Cooling hysteresis 00000001H to 0000270FH (0.1 to 999.9)
Variable
type
Address ch Setting data name Description