94
Variable Area Map Section 5-10
C3 0000 - Input type Platinum-resistance thermometer input type:
00000000H (0): Pt (−200 to 850°C or −300 to 1,500°F)
00000001H (1): Pt (−199.9 to 500.0°C or −199.9 to 900.0°F)
00000002H (2): Pt (0.0 to 100°C or 0.0 to 210.0°F)
00000003H (3): JPt (−199.9 to 500.0°C or −199.9 to 900.0°F)
00000004H (4): JPt (0.0 to 100.0°C or 0.0 to 210.0°F)
Thermocouple input type:
00000000H (0): K (−200 to 1,300°C or −300 to 2,300°F)
00000001H (1): K (−20.0 to 500.0°C or 0.0 to 900.0°F)
00000002H (2): J (−100 to 850°C or −100 to 1,500°F)
00000003H (3): J (−20.0 to 400.0°C or 0.0 to 750.0°F)
00000004H (4): T (−200 to 400°C or −300 to 700°F)
00000005H (5): E (0 to 600°C or 0 to 1,100°F)
00000006H (6): L (−100 to 850°C or −100 to 1,500°F)
00000007H (7): U (−200 to 400°C or −300 to 700°F)
00000008H (8): N (−200 to 1,300°C or −300 to 2,300°F)
00000009H (9): R (0 to 1,700°C or 0 to 3,000°F)
0000000AH (10): S (0 to 1,700°C or 0 to 3,000°F)
0000000BH (11): B (100 to 1,800°C or 300 to 3,200°F)
0000000CH (12): Infrared temperature sensor (K10 to 70°C)
0000000DH (13): Infrared temperature sensor (K60 to 120°C)
0000000EH (14): Infrared temperature sensor (K115 to 165°C)
0000000FH (15): Infrared temperature sensor (K160 to 260°C)
00000010H (16): 0 to 50 mV
00000011H (17): T (−199.9 to 400.0°C or −199.9 to 700.0°F)
00000012H (18): U (−199.9 to 400.0°C or −199.9 to 700.0°F)
0001 1 Scaling upper limit Scaling lower limit + 1 to 0000270FH (scaling lower limit + 1 to
9,999)
0002 Scaling lower limit FFFFF831H to scaling upper limit −1 (−1,999 to scaling upper
limit − 1)
0003 Decimal point position 00000000H to 00000001H (0 to 1)
0004 - Temperature units 00000000H (0): °C
00000001H (1): °F
0005 1 SP upper limit Temperature: SP lower limit + 1 to input range upper limit
Analog: SP lower limit + 1 to scaling upper limit
0006 SP lower limit Temperature: Input range lower limit to SP upper limit − 1
Analog: Scaling lower limit to SP upper limit −1
0007 PID/OnOff 00000000H (0): ON/OFF
00000001H (1): 2-PID control
0008 Heating control period 00000001H to 00000063H (1 to 99)
0009 Cooling control period 00000001H to 00000063H (1 to 99)
000A Direct/reverse operation 00000000H (0): Reverse operation
00000001H (1): Direct operation
Variable
type
Address ch Setting data name Description