95
Variable Area Map Section 5-10
C3 000B 1 Alarm 1 type 00000000H (0): No alarm function
00000001H (1): Upper and lower limit alarm
00000002H (2): Upper limit alarm
00000003H (3): Lower limit alarm
00000004H (4): Upper and lower limit range alarm
00000005H (5): Upper and lower limit alarm with standby
sequence
00000006H (6): Upper limit alarm with standby sequence
00000007H (7): Lower limit alarm with standby sequence
00000008H (8): Absolute value upper limit alarm
00000009H (9): Absolute value lower limit alarm
0000000AH (10): Absolute value upper limit alarm with standby
sequence
0000000BH (11): Absolute value lower limit alarm with standby
sequence
000C Alarm 2 type Same as for alarm 1 type
000D Alarm 3 type Same as for alarm 1 type
000E - Control output 1 alloca-
tion
00000000H (0): Heating control output for ch1
00000001H (1): Cooling control output for heating/cooling con-
trol for ch1
00000002H (2): Alarm 1 and HB alarm OR output for ch1 (See
note 1.)
Alarm 1 and sensor error alarm OR output for
ch1 (See note 2.)
00000003H (3): Alarm 2 output for ch1
00000004H (4): Alarm 3 output for ch1
00000005H (5): Heating control output for ch2
00000006H (6): Cooling control output for heating/cooling con-
trol for ch2
00000007H (7): Alarm 1 and HB alarm OR output for ch2 (See
note 1.)
Alarm 1 and sensor error alarm OR output for
ch2 (See note 2.)
00000008H (8): Alarm 2 output for ch2
00000009H (9): Alarm 3 output for ch2
0000000AH (10): SP transfer output for ch1 (See note 2.)
0000000BH (11): Ramp SP transfer output for ch1
(See note 2.)
0000000CH (12): PV transfer output for ch1
(See note 2.)
0000000DH (13): Heating MV transfer output for ch1
(See note 2.)
0000000EH (14): Cooling MV transfer output for ch1
(See note 2.)
0000000FH (15): SP transfer output for ch2
(See note 2.)
00000010H (16): Ramp SP transfer output for ch2
(See note 2.)
00000011H (17): PV transfer output for ch2
(See note 2.)
00000012H (18): Heating MV transfer output for ch2
(See note 2.)
00000013H (19): Cooling MV transfer output for ch2
(See note 2.)
000F Control output 2 alloca-
tion
Same as for control output 1 allocation
Variable
type
Address ch Setting data name Description