Variable Area Map Section 5-10
C3 0010 - Auxiliary output 1 alloca-
tion
00000000H (0): Heating control output for ch1
00000001H (1): Cooling control output for heating/cooling con-
trol for ch1
00000002H (2): Alarm 1 and HB alarm OR output for ch1 (See
note 1.)
Alarm 1 and sensor error alarm OR output for
ch1 (See note 2.)
00000003H (3): Alarm 2 output for ch1
00000004H (4): Alarm 3 output for ch1
00000005H (5): Heating control output for ch2
00000006H (6): Cooling control output for heating/cooling con-
trol for ch2
00000007H (7): Alarm 1 and HB alarm OR output for ch2 (See
note 1.)
Alarm 1 and sensor error alarm OR output for
ch2 (See note 2.)
00000008H (8): Alarm 2 output for ch2
00000009H (9): Alarm 3 output for ch2
0011 Auxiliary output 2 alloca-
tion
Same as for control output 1 allocation
0012 Operation after power
ON
00000000H (0): Stop
00000001H (1): Continue (Continues the operation status from
before the power supply was stopped.)
0013 Communications data
length
00000007H (7): 7
00000008H (8): 8
0014 Communications stop bit 00000001H (1): 1
00000002H (2): 2
0015 Communications parity 00000000H (0): None
00000001H (1): Even
00000002H (2): Odd
0016 Communications
response transmission
wait time
00000000H to 0000270FH (0 to 9,999)
0017 No. of multi-SP uses 00000000H (0): No multi-SP
00000001H (1): Switch between SP0/1
0018 Event input function 00000000H (0): Non
00000001H (1): RUN/STOP
0019 Use multi-SP 00000000H (0): OFF
00000001H (1): ON
001A 1 SP ramp setting 00000000H (0): OFF
00000001H to 0000270FH (1 to 9,999)
001B - Standby sequence restart 00000000H (0): Condition A
00000001H (1): Condition B
001C 1 Alarm 1 open in alarm 00000000H (0): Closed
00000001H (1): Open
001D Alarm 1 hysteresis 00000001H to 0000270FH (0.1 to 999.9)
001E 1 Alarm 2 open in alarm 00000000H (0): Closed
00000001H (1): Open
001F Alarm 2 hysteresis 00000001H to 0000270FH (0.1 to 999.9)
0020 Alarm 3 open in alarm 00000000H (0): Closed
00000001H (1): Open
0021 Alarm 3 hysteresis 00000001H to 00002702FH (0.1 to 999.9)
Variable
type
Address ch Setting data name Description