185
Appendix B
Sensor Input Setting Ranges/Control Ranges
• Default is 0.
• The applicable standards for each of the above input ranges are as follows:
• K, J, T, E, N, R, S, B: JIS C1602-1995, IEC 584-1
• L: Fe-CuNi, DIN 43710-1985
• U: Cu-CuNi, DIN 43710-1985
• JPt100: JIS C 1604-1989, JIS C 1606-1989
• Pt100: JIS C 1604-1997 IEC 751
Sensor Input
type
Name Set
value
Input temperature setting range Control range
Platinum
resis-
tance
ther-
mometer
input
type
Plati-
num
resis-
tance
ther-
mometer
Pt100
0 −200 to 850°C or −300 to 1,500°F −220 to 870°C or −340 to 1,540°F
1 −199.9 to 500.0°C or −199.9 to 900.0°F −219.9 to 520.0°C or −239.9 to 940.0°F
2 0.0 to 100.0°C or 0.0 to 210.0°F −20.0 to 120.0°C or −40.0 to 250.0°F
JPt100 3 −199.9 to 500.0°C or −199.9 to 900.0°F −219.9 to 520.0°C or −239.9 to 940.0°F
4 0.0 to 100.0°C or 0.0 to 210.0°F −20.0 to 120.0°C or −40.0 to 250.0°F
Thermo-
couple
input
type
Thermo-
couple
K
0 −200 to 1,300°C or −300 to 2,300°F −220 to 1,320°C or −340 to 2,340°F
1 −20.0 to 500.0°C or 0.0 to 900.0°F −40.0 to 520.0°C or −40.0 to 940.0°F
J2−100 to 850°C or −100 to 1,500°F −120 to 870°C or −140 to 1540°F
3 −20.0 to 400.0°C or 0.0 to 750.0°F −40.0 to 420.0°C or −40.0 to 790.0°F
T4−200 to 400°C or −300 to 700°F −220 to 420°C or −340 to 740°F
17 −199.9 to 400.0°C or −199.9 to 700.0°F −219.9 to 420.0°C or −239.9 to 740.0°F
E 5 0 to 600°C or 0 to 1,100°F −20 to 620°C or −40 to 1,140°F
L6−100 to 850°C or −100 to 1,500°F −120 to 870°C or −140 to 1,540°F
U7−200 to 400°C or −300 to 700°F −220 to 420°C or −340 to 740°F
18 −199.9 to 400.0°C or −199.9 to 700.0°F −219.9 to 420.0°C or −239.9 to 740.0°F
N8−200 to 1,300°C or −300 to 2,300°F −220 to 1,320°C or −340 to 2,340°F
R 9 0 to 1,700°C or 0 to 3,000°F −20 to 1,720°C or −40 to 3,040°F
S 10 0 to 1,700°C or 0 to 3,000°F −20 to 1,720°C or −40 to 3,040°F
B 11 100 to 1,800°C or 300 to 3,200°F 0 to 1,820°C or 0 to 3,240°F
ES1A
Infrared
Temper-
ature
Sensor
K10 to
70°C
12 0 to 90°C or 0 to 190°F −20 to 130°C or −40 to 270°F
K60 to
120°C
13 0 to 120°C or 0 to 240°F −20 to 160°C or −40 to 320°F
K115 to
165°C
14 0 to 165°C or 0 to 320°F −20 to 205°C or −40 to 400°F
K160 to
260°C
15 0 to 260°C or 0 to 500°F −20 to 300°C or −40 to 580°F
Analog
input
0 to
50 mA
16 One of the following ranges depending
on the results of scaling:
−1,999 to 9,999 or −199.9 to 999.9
−5% to 105% of setting range