186
Sensor Input Setting Ranges/Control Ranges Appendix B
List of E5ZN-SDL Settings
Operation Level
Adjustment Level
Parameter No. 1 display:
Characters
No. 2 display:
Default
Setting (monitor) value
PV --- Displayed when a screen for PV display only
has been added in additional PV display
(advanced function setting level).
PV/SP 0 Temperature: Range specified for sensor input
Analog: Scaling lower limit −5% FS to scaling
upper limit +5% FS
Multi-SP n-sp 0 0: SP0, 1: SP1
Ramp SP value monitor sp-n 0 SP lower limit to SP upper limit
Heater current value monitor ct 0.0 0.0 to 55.0 (pulse output models only)
RUN/STOP r-s stop run: Start operation, stop: Stop operation
Alarm value 1 al-1 0 −1999 to 1999/−199.9 to 999.9
Alarm upper limit value 1 al-1h 0 −1999 to 1999/−199.9 to 999.9
Alarm lower limit value 1 al-1l 0 −1999 to 1999/−199.9 to 999.9
Alarm value 2 al-2 0 −1999 to 1999/−199.9 to 999.9
Alarm upper limit value 2 al-2h 0 −1999 to 1999/−199.9 to 999.9
Alarm lower limit value 2 al-2l 0 −1999 to 1999/−199.9 to 999.9
Alarm value 3 al-3 0 −1999 to 1999/−199.9 to 999.9
MV monitor for heating o0.0Standard control: −5.0 to 105.0
Heating and cooling control: 0.0 to 105.0
MV monitor for cooling c-o 0.0 Heating and cooling control: 0.0 to 105.0
Parameter No. 1 display:
Characters
No. 2 display:
Default
Setting (monitor) value
AT execute/cancel at off on: AT execute, off: AT cancel
Communications writing cmwt on on: Enabled, off: Disabled
Heater current value monitor ct 0.0 0.0 to 55.0 (pulse output models only)
Heater burnout detection hb 0.0 0.0 to 55.0 (pulse output models only)
SP 0 sp-0 0 SP lower limit to SP upper limit
SP 1 sp-1 0 SP lower limit to SP upper limit
Temperature input shift ins 0.0 −199.9 to 999.9
Upper limit temperature input
shift value
insh 0.0 −199.9 to 999.9
Lower limit temperature input
shift value
insl 0.0 −199.9 to 999.9
Proportional band p8.00.1 to 999.9
Integral time i 233 0 to 3999
Derivative time d400 to 3999
Cooling coefficient c-sc 1.00 0.01 to 99.99
Dead band c-db 0.0 −199.9 to 999.9
Manual reset value of-r 50.0 1.1 to 100.0
Heating hysteresis hys 1.0 0.1 to 999.9
Cooling hysteresis chys 1.0 0.1 to 999.9