187
Sensor Input Setting Ranges/Control Ranges Appendix B
Initial Setting Level
Parameter No. 1 display:
Characters
No. 2 display:
Default
Setting (monitor) value
Input type in-t 0 Platinum-resistance thermometer input:
0: Pt (−200 to 850°C or −300 to 1,500°F)
1: Pt (−199.9 to 500.0°C or −199.9 to
900.0°F)
2: Pt (0.0 to 100°C or 0.0 to 210.0°F)
3: JPt (−199.9 to 500.0°C or −199.9 to
900.0°F)
4: JPt (0.0 to 100.0°C or 0.0 to 210.0°F)
0 Thermocouple input:
0: K (−200 to 1,300°C or −300 to 2,300°F)
1: K (−20.0 to 500.0°C or 0.0 to 900.0°F)
2: J (−100 to 850°C or −100 to 1,500°F)
3: J (−20.0 to 400.0°C or 0.0 to 750.0°F)
4: T (−200 to 400°C or −300 to 700°F)
5: E (0 to 600°C or 0 to 1,100°F)
6: L (−100 to 850°C or −100 to 1,500°F)
7: U (−200 to 400°C or −300 to 700°F)
8: N (−200 to 1,300°C or −300 to 2,300°F)
9: R (0 to 1,700°C or 0 to 3,000°F)
10: S (0 to 1,700°C or 0 to 3,000°F)
11: B (100 to 1,800°C or 300 to 3,200°F)
12: Infrared temperature sensor
(K10 to 70°C)
13: Infrared temperature sensor
(K60 to 120°C)
14: Infrared temperature sensor
(K115 to 165°C)
15: Infrared temperature sensor
(K160 to 260°C)
16: 0 to 50 mV
17: T (−199.9 to 400.0°C or −199.9 to
700.0°F)
18: U (−199.9 to 400.0°C or −199.9 to
700.0°F)
Scaling upper limit in-h 100 Scaling lower limit + 1 to 9999
Scaling lower limit in-l 0 −1999 to scaling upper limit −1
Decimal point dp 0 0: 0000 1: 000.0
°C/°F selection d-u c c: °C, f: °F
SP upper limit sl-h 850 (Pt)/ 1300 (TC) Temperature: SP lower limit +1 to input range
upper limit
Analog: SP lower limit +1 to scaling upper
limit
SP lower limit sl-l -200 Temperature: Input range lower limit to SP
upper limit −1
Analog: SP lower limit +1 to scaling upper
limit
PID/OnOff cntl pid onof: ON/OFF control, pid: 2-PID control
Heating control period cp 2 1 to 99
Cooling control period c-cp 2 1 to 99
Direct/reverse operation oreU or-r or-r: Reverse operation or-d: Direct opera-
tion