188
Sensor Input Setting Ranges/Control Ranges Appendix B
Alarm 1 type alt1 2 0: No alarm function
1: Upper and lower limit alarm
2: Upper limit alarm
3: Lower limit alarm
4: Upper and lower limit range alarm
5: Upper and lower limit alarm with standby
sequence
6: Upper limit alarm with standby sequence
7: Lower limit alarm with standby sequence
8: Absolute value upper limit alarm
9: Absolute value lower limit alarm
10: Absolute value upper limit alarm with
standby sequence
11: Absolute value lower limit alarm with
standby sequence
Alarm 2 type alt2 2 Same as for alarm 1 type.
Alarm 3 type alt3 2 Same as for alarm 1 type.
Control output 1 allocation out1 0 0: Heating control output for ch1
1: Cooling control output for ch1
2: Alarm 1 and HB alarm OR output for ch1
(pulse output models only)
Alarm 1 and sensor error alarm OR output
for ch1 (analog output models only)
3: Alarm 2 output for ch1
4: Alarm 3 output for ch1
5: Heating control output for ch2
6: Cooling control output for ch2
7:Alarm 1 and HB alarm OR output for ch2
(pulse output models only)
Alarm 1 and sensor error alarm OR output
for ch2 (analog output models only)
8: Alarm 2 output for ch2
9: Alarm 3 output for ch2
10: SP transfer output for ch1 (analog output
models only)
11: Ramp SP transfer output for ch1 (analog
output models only)
12: PV transfer output for ch1 (analog output
models only)
13: Heating MV transfer output for ch1(analog
output models only)
14: Cooling MV transfer output for ch1 (ana-
log output models only)
15: SP transfer output for ch2 (analog output
models only)
16: Ramp SP transfer output for ch2 (analog
output models only)
17: PV transfer output for ch2 (analog output
models only)
18: Heating MV transfer output for ch2 (ana-
log output models only)
19: Cooling MV transfer output for ch2 (ana-
log output models only)
Control output 2 allocation out2 5 Same as for control output 1 allocation.
Parameter No. 1 display:
Characters
No. 2 display:
Default
Setting (monitor) value