Sensor Input Setting Ranges/Control Ranges Appendix B
Auxiliary output 1 allocation sub1 2 0: Heating control output for ch1
1: Cooling control output for ch1
2: Alarm 1 and HB alarm OR output for ch1
(pulse output models only)
Alarm 1 and sensor error alarm OR output
for ch1 (analog output models only)
3: Alarm 2 output for ch1
4: Alarm 3 output for ch1
5: Heating control output for ch2
6: Cooling control output for ch2
7: Alarm 1 and HB alarm OR output for ch2
(pulse output models only)
Alarm 1 and sensor error alarm OR output
for ch2 (analog output models only)
8: Alarm 2 output for ch2
9: Alarm 3 output for ch2
Auxiliary output 2 allocation sub2 7 Same as auxiliary output 1 allocation.
Auxiliary output 3 allocation sub3 12 Same as control output 1
allocation.
Analog output
models only
Auxiliary output 4 allocation sub4 17 Same as control output 1
allocation.
Operation after power ON cont no no: Stop, yes: Continue (Continues the opera-
tion status from before the power supply was
stopped.)
OUT1 transfer output upper
limit
tr1h 850 (Pt)/ 1300 (TC) 1999 to 9999 or 199.9 to
999.9
Analog output
models only
OUT1 transfer output lower
limit
tr1l -200 1999 to 9999 or 199.9 to
999.9
OUT2 transfer output upper
limit
tr2h 850 (Pt)/ 1300 (TC) 1999 to 9999 or 199.9 to
999.9
OUT2 transfer output lower
limit
tr2l -200 1999 to 9999 or 199.9 to
999.9
SUB3 transfer output upper
limit
tr3h 850 (Pt)/ 1300 (TC) 1999 to 9999 or 199.9 to
999.9
SUB3 transfer output lower
limit
tr3l -200 1999 to 9999 or 199.9 to
999.9
SUB4 transfer output upper
limit
tr4h 850 (Pt)/ 1300 (TC) 1999 to 9999 or 199.9 to
999.9
SUB4 transfer output lower
limit
tr4l -200 1999 to 9999 or 199.9 to
999.9
Current output type ot-1 0 0: 4 to 20 mA DC,
1: 0 to 20 mA DC
Analog output
models only
Voltage output type ot-2 0 0: 1 to 5 VDC, 1: 0 to 5 VDC
Sensor error indicator used sedu 3 0: Indicators always not lit
(both ch1 and ch2)
1: Sensor error indicator lit
(ch1 only)
2: Sensor error indicator lit
(ch2 only)
3: Sensor error indicators lit
(both ch1 and ch2)
Upgraded
pulse output
models and
analog output
models only
Move to advanced function
setting level
amoU 0 1999 to 9999
Parameter No. 1 display:
Characters
No. 2 display:
Default
Setting (monitor) value