EasyManua.ls Logo

Parker 690+ series - Example Commands

Parker 690+ series
242 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Sequencing Logic 4-5
690+ Series Frequency Inverter
(Not) Quick Stop
ANDed with the NOT FAST STOP parameter on the SEQUENCING LOGIC function block.
When both Set (=1) is the same as:
NOT FAST STOP = TRUE
When either or both Cleared (= 0) is the same as :
NOT FAST STOP = FALSE
Enable Operation
ANDed with the DRIVE ENABLE parameter on the SEQUENCING LOGIC function block.
When both Set (=1) is the same as:
DRIVE ENABLE = TRUE
When either or both Cleared (= 0) is the same as :
DRIVE ENABLE = FALSE
Enable Ramp Output, Enable Ramp, Enable Ramp Input
Not implemented. The state of these bits must be set (=1) to allow this feature to be added in the
future.
Reset Fault
Replaces the REM TRIP RESET parameter on the SEQUENCING LOCIC function block.
When Set (=1) is the same as:
REM TRIP RESET = TRUE
When Cleared (= 0) is the same as :
REM TRIP RESET = FALSE
Remote
Not implemented. It is intended to allow the PLC to toggle between local and remote. The state
of this must be set (=1) to allow this feature to be added in the future.
Example Commands
047F hexadecimal to RUN
047E hexadecimal to STOP

Table of Contents

Related product manuals