1-96 Programming Your Application
690+ Series Frequency Inverter
SEQUENCING LOGIC
This function block contains all the
parameters relating to the sequencing
(start and stop) of the Inverter.
Before the Inverter will respond to the
RUN FWD, RUN REV or JOG
parameters (cause the Inverter to run
or jog), the parameters DRIVE
ENABLE, NOT FAST STOP and
NOT COAST STOP need to be set to
TRUE. In addition, the Inverter needs
to be healthy (HEALTHY is TRUE).
The Inverter will only respond to
RUN FWD, RUN REV and JOG if
the Inverter is in the Remote
Sequencing mode.
If RUN FWD and RUN REV are
TRUE, both are ignored and the
Inverter will stop.
Sequencing Logic
TRIPPED [289]
FALSE
RUNNING [285]
FALSE
JOGGING [302]
FALSE
STOPPING [303]
FALSE
OUTPUT CONTACTOR [286]
FALSE
SWITCH ON ENABLE [288]
FALSE
SWITCHED ON [306]
FALSE
READY [287]
FALSE
SYSTEM RESET [305]
FALSE
SEQUENCER STATE [301]
START DISABLED
REMOTE REV OUT [296]
FALSE
HEALTHY [274]
TRUE
FAN RUNNING [620]
FALSE
0.000s
[1686] START DELAY
FALSE
[291] RUN FORWARD
FALSE
[292] RUN REVERSE
FALSE
[293] NOT STOP
FALSE
[280] JOG
TRUE
[1235] CONTACTOR CLOSED
TRUE
[276] DRIVE ENABLE
TRUE
[277] NOT FAST STOP
TRUE
[278] NOT COAST STOP
FALSE
[294] REMOTE REVERSE
FALSE
[282] REM TRIP RESET
TRUE
[290] TRIP RST BY RUN
FALSE
[283] POWER UP START
MMI Menu Map
1
SETUP
2
SEQ & REF
3
SEQUENCING LOGIC
START DELAY
RUN FORWARD
RUN REVERSE
NOT STOP
JOG
CONTACTOR CLOSED
DRIVE ENABLE
NOT FAST STOP
NOT COAST STOP
REMOTE REVERSE
REM TRIP RESET
TRIP RST BY RUN
POWER UP START
TRIPPED
RUNNING
JOGGING
STOPPING
OUTPUT CONTACTOR
SWITCH ON ENABLE
SWITCHED ON
READY
SYSTEM RESET
SEQUENCER STATE
REMOTE REV OUT
HEALTHY
FAN RUNNING
Parameter Descriptions
START DELAY
Range: 0.000 to 30.000s
Delays the action of "ramping to setpoint" from the Run command. This can allow a period for
motor flux to establish before the ramp to setpoint.
RUN FWD
Range: FALSE / TRUE
Setting this parameter to TRUE causes the Inverter to run in the forward direction.
RUN REV
Range: FALSE / TRUE
Setting this parameter to TRUE causes the Inverter to run in the reverse direction.
NOT STOP
Range: FALSE / TRUE
Setting this parameter TRUE will latch the RUN FWD or RUN REV commands. Once latched,
they can be reset to FALSE and the Inverter will continue to run. Setting NOT STOP to FALSE
causes the run commands to be unlatched.
JOG
Range: FALSE / TRUE
Setting this parameter TRUE causes the Inverter to run at the speed set by JOG SETPOINT
(refer to the REFERENCE JOG function block). Once jogging, setting JOG to FALSE causes
the Inverter to ramp to zero.
CONTACTOR CLOSED
Range: FALSE / TRUE
Feedback used to indicate that the external contactor has been closed. It must be TRUE for the
sequencer to proceed from the SWITCHED ON state to the READY STATE, refer to
SEQUENCER STATE.
DRIVE ENABLE
Range: FALSE / TRUE
This provides a means of electronically inhibiting Inverter operation. Whilst running, setting this
parameter to FALSE disables the Inverter operation and causes the motor to coast.
NOT FAST STOP
Range: FALSE / TRUE
Whilst running or jogging, setting this parameter to FALSE causes the Inverter to ramp to zero.
The rate is set by FAST STOP RATE in the STOP function block. The action of setting NOT
FAST STOP to TRUE is latched. The Inverter cannot be restarted until fast stop is completed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker 690+ series and is the answer not in the manual?

Parker 690+ series Specifications

General IconGeneral
Frequency50/60 Hz
Overload150% for 60 seconds
Communication OptionsEthernet
Protection RatingIP20
Operating Temperature0°C to 55°C
ProgrammabilityYes
Communication PortsRS485
I/O CapabilityDigital and Analog I/O
Programming LanguagesFunction Block Diagram
DimensionsVaries by module

Related product manuals