EasyManuals Logo

Parker 690+ series User Manual

Parker 690+ series
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
1-14 Programming Your Application
690+ Series Frequency Inverter
Examples
Unipolar TYPE 0..+10V adjusted by the OFFSET parameter to give a bipolar reading.
Bipolar TYPE -10..+10V giving a bipolar reading.
Unipolar TYPE 0..20mA giving a unipolar reading.
+100%
10V (100%)
0%
5V (50%)
-100%
0V (0%)
VALUE
Parameter
200%
TYPE
Parameter
SCALE Parameter = 50% (200 x 0.5 = 100%)
OFFSET Parameter = 50% (10 x 0.5 = 5V)
TYPE Parameter = 0..+10V
100%
OFFSET
+100%
+10V (100%)
0%
0V (0%)
-100%
-10V (-100%)
VALU
E
Parameter
200%
TYPE
Parameter
SCALE Parameter = 100% (no effect)
OFFSET Parameter = 0% (no effect)
TYPE Parameter = -10..+10V
200%
100%
20mA (100%)
50%
10mA (50%)
0%
0mA (0%)
VALU
E
Parameter
100%
TYPE
Parameter
SCALE Parameter = 100% (no effect)
OFFSET Parameter = 0% (no effect)
TYPE Parameter = 0..+20mA
100%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker 690+ series and is the answer not in the manual?

Parker 690+ series Specifications

General IconGeneral
Frequency50/60 Hz
Overload150% for 60 seconds
Communication OptionsEthernet
Protection RatingIP20
Operating Temperature0°C to 55°C
ProgrammabilityYes
Communication PortsRS485
I/O CapabilityDigital and Analog I/O
Programming LanguagesFunction Block Diagram