3.5 Diagnostics and status indicators
The diagnostics and status indicators are used for quick local error diagnostics.
Figure 3-7 Diagnostics and status indicators
X4
UL
UL
ETH
PWR
PN/AXC/PLC
BF-C
BF-D
SF
BF-D
SF
BF-C
D
E
Table 3-1 Controller diagnostics and status indicators
Desig-
nation
Color Meaning Status Description
PN: PROFINET controller/device function
BF-C Red
PROFINET con-
troller:
Communication
error (bus fault)
AXC F 1050 as a PROFINET controller
Off
– The AXC F 1050 has established an active communication
connection to each configured PROFINET device.
Or:
– The PROFINET controller function is switched off.
On
No link status on the Ethernet interfaces and/or no 100 Mbit
transmission and/or no full duplex mode.
Flashing
(1 Hz)
Link status present, at least one configured PROFINET device
does not have a communication connection.
BF-D Red
PROFINET
device:
Communication
error (bus fault)
AXC F 1050 as a PROFINET device
Off
– A PROFINET controller has established an active commu-
nication connection to the AXC F 1050 (PROFINET de-
vice)
Or:
– The PROFINET device function is switched off.
On
No PROFINET communication (no link status at the Ethernet in-
terfaces).
Flashing
(1 Hz)
Link status present, no communication connection to the
PROFINET controller.
SF Red
Group error
(PROFINET)
Off PROFINET diagnostics not present.
On PROFINET diagnostics present.