70
Programming the System
Hunter-Pro Series & Captain 8 Installation Guide
6.10.6 Outputs in expanders
Configure the outputs of the OUT-1000
1
, I/O-R and I/O-8N expansion cards.
6.10.6.1 Examples
1. ON/OFF output (only in Hunter-Pro Series):
Set the ON/OFF output to be triggered every time a zone is opened, by using the "Open Zone"
output type.
The procedure is as follows:
a) Enter the ON/OFF (physical) output screen.
b) Select the output type that will trigger it. In this example, it is the default “Zone open”
output type.
c) Set which partition/s can trigger this output type.
d) Set the polarity of the output.
2. PGM output (only in Captain 8):
Set the "Burgl. -All Types" output type (i.e. all the burglary output types) to trigger the PGM
output. This means that the PGM output will be triggered with any burglary zone alarm.
6.11 Key 8: Full Programming
See the menu screens in section B.7, on page 101.
6.11.1 System defaults
Initialize the system to the factory defaults. This will reset all the inforamtion stored in the
control panel, including zone settings and names.
1. Press [ENTR] -> "Are you sure?"
2. Press [ENTR] to approve; a countdown will start.
3. Press [END] when the countdown expires.
1
Obsolete product