Troubleshooting
87
Hunter-Pro Series & Captain 8 Installation Guide
Fault
Cause & action to take
System Error
The EPROM version and the panel’s software version do not match. Contact your
dealer
Int. siren fault
1
The internal siren’s wires are cut/shortened
Ext. siren fault
1
The external siren’s wires are cut/shortened
Video 1 fault
No communication with video module #1 (only for serial connected modules)
Video 2 fault
1
No communication with video module #2 (only for serial connected modules)
Video 3 fault
1
No communication with video module #3 (only for serial connected modules)
Video 4 fault
1
No communication with video module #4 (only for serial connected modules)
Video 1 power fault
Voltage fault in video module #1
Video 2 power fault
1
Voltage fault in video module #2
Video 3 power fault
1
Voltage fault in video module #3
Video 4 power fault
1
Voltage fault in video module #4
net4pro fault
No communication with the net4pro
9.2.1 Radio faults
Check that:
1. The radio transmitter is correctly connected.
2. The radio account number is not zero.
3. The Radio format is compatible with that of the Central Station.
4. The antenna is intact, not bended and is attached vertically.
5. If the antenna is installed away from the transmitter, check the cable.
9.2.2 Dialer faults
To test the dialer: arm the panel, open a zone and wait for a call. Do not disarm the panel
before receiving the call, because disarming immediately after alarm stops the dialer.
Make sure that:
1. The telephone wires are connected right.
2. At least one private telephone number is set and is correct.
3. In theCommunication options” menu, “P - Connected T.Line” is set to “+” (see section
6.5.4, on page 54).
4. The parameters in the “Private Dialer menu are set correctly (see section 6.5.10, on
page 54).
5. A prefix is set, if required.
9.2.3 Incoming phone call faults
If the panel does not receive calls, make sure that:
1. In theCommunication options” menu, “P - Connected T.Line” is set to “+” (see section
6.5.4, on page 54).
2. The number of rings reaches its limit (see section 6.5.4.1, on page 55).
3. The telephone wires are connected right.
1
Not in use in Captain 8.