Page 115 
The  fourth  parameter  and  the  fifth  parameter  for  each  relay  set  the 
Alarm “ON” and “OFF” points. For a high alarm the “ON” is set higher 
than “OFF”. For low alarm then “ON” is set lower than “OFF”. See the 
appropriate  alarm  ID,  table (P*212, 222, 232, 242, 252, 262) for further 
information. 
When P*211, 221, 231, 241, 251, 261 = 1 (Level), 2 (Rate of Change) or 3 
(Temp.)   
P*213, P*223, P*233 P*243, P*253, P*263 - Relay Setpoint 1 
Determines  the  “ON”  or  “OFF”  point  for  the  alarm  according  to  the  ID 
selected. 
P*214, P*224, P*234, P*244, P*254, P*264 - Relay Setpoint 2 
Determines  the  “ON”  or  “OFF”  point  for  the  alarm  according  to  the  ID 
selected. 
Important Information 
Setpoints are entered in values according to the function selected.  
Level - entered in Display Units or % of span as referenced to Empty 
Level.            
Rate of Change - entered in Display Units per minute or % of span per 
minute. For an alarm on a increasing level enter setpoints as a positive 
value, for an alarm on a decreasing level enter setpoints as a negative 
value.              
Temperature - entered in ºC.   
Efficiency – entered in % value of efficiency. 
See the appropriate alarm function, table (P211, 221, 231, 241, 251, 
261) for further information.   
 
 
  To set level setpoints in % press the   hot key to show and enter % 
figure relative to empty level.  
When P*211, 221, 231, 241, 251, 261 = 4 (Loss of Echo), 5 (Loss of 
Clock), 6 (Device Fail) or 7 (Device Alarm) 
 The fourth and fifth parameters have no function and will not be 
displayed.