If a pump fails to meet the demand (due 
to malfunction, intake blockage etc.), 
then it is stopped and another pump shall 
take over. Each pump has its own 
setpoints, (P*213, 223, 233, 243, 253, 
263 & P*214, 224, 234, 244, 254, 264) 
but each time all pumps have stopped, 
then the setpoints are sequentially 
rotated between the pumps to ensure 
equal pump use. 
5= Duty backup and assist 
First pump comes on, if it cannot cope, 
it goes off and next pump comes on 
(duty backup). This continues until the 
last pump comes on and if it cannot cope 
the first pump comes back on to assist 
the last pump  (duty assist) if the level 
continues to rise all other pumps will 
come on (assist) in turn until the level 
decreases to the pump off points. Each 
pump has its own setpoints, (P*213, 
223, 233, 243, 253, 263 & P*214, 224, 
234, 244, 254, 264). 
6= Service ratio duty assist 
All pumps are used to assist each other 
(run at the same time) and each pump 
has its own setpoints (P*213, 223, 233, 
243, 253, 263 & P*214, 224, 234, 244, 
254, 264). And a service ratio setting. 
The third setpoint (P*215, 225, 235, 
245, 255, 265) is used to set the service 
ratio. Each time a pump is required to 
start then the pump with the least 
running hours (with respect to the 
service ratio) is started (i.e. the setpoints 
are re-assigned accordingly).    
For example, if two pumps A and B 
have the service ratio set to 2 and 1 
respectively, then pump A will operate 
for twice as many hours as pump B.