7= Service ratio duty backup 
If a pump fails to meet the demand (due 
to malfunction, intake blockage and so 
on), then it is stopped and another pump 
shall take over. Each time a pump is 
required to start then the pump with the 
least running hours (with respect to the 
service ratio) is started (i.e. the setpoints 
are re-assigned accordingly). Each pump 
has its own setpoints (P*213, 223, 233, 
243, 253, 263 & P*214, 224, 234, 244, 
254, 264). The third setpoint (P*215, 
225, 235, 245, 255, 265) is used to set 
the service ratio. For example, if two 
pumps A and B have the service ratio set 
to 2 and 1 respectively, then pump A 
will operate for twice as many hours as 
pump B. 
8= First On First Off, 
alternate duty assist 
The first pump switched on is the first 
pump to be switched off, etc. regardless 
of the set points, so the setpoints are 
dynamically changed to enable this. 
9 = Service Ratio Standby 
When a service ratio duty is being used, 
on all other pumps in use, the standby 
pump can be started on a ratio basis 
only, when it will assume the setpoints 
of the next pump to start. The third 
setpoint (P*215, 225, 235, 245, 255, 
265) is used to set the service ratio. 
There are four pumps. Two rotate their 
start-up sequence with each other. If the 
two pumps cannot keep up, the level rise 
to the setpoints of the other two pumps 
which take over and rotate their 
sequence with each other. 
Important Information 
The pumps are started and stopped at the “ON” and “OFF” setpoints. To 
pump down (reduce level) then set “ON” higher than “OFF”. To pump up 
(increase level) then set “ON” lower than “OFF”.