Step Time Control allows relays to be used to 
control a device, such as a motorised valve or 
gate, in order to maintain the level within two 
predetermined points. Relays will energise 
“ON” when Step Time condition is in effect 
and de-energises “OFF” when Step Time 
goes off. One relay will be required to control 
an increase in level, (‘open’ the device) and a 
second relay is required to control a decrease 
in level, (‘close’ the device). Alarm ID 
(P*212, 222, 232, 242, 252, 262) is used to 
assign the relay to control either the open or 
close condition. Step Time Control relay 
requires three setpoints. The first set point 
(P*213, 223, 233, 243, 253, 263) determines 
the level, at which the relay is to be activated, 
(N.B. level setpoint for open relay, increase 
the level, must be lower than the setpoint for 
the close relay, decrease the level). The relay 
will energise “ON” after the Limit time that 
is set in Relay Setpoint 3 (P*215, 225, 235, 
245, 255, 265). And turns “OFF”, de-
energises, after the Drive Period that is set in 
Relay Setpoint 2 (P*214, 224, 234, 244, 254, 
264). 
Control is based on the level in the vessel. All 
general controls are used to assist each other 
(run at the same time) and each general 
control relay has its own “ON” and “OFF” 
setpoints. Two setpoints are required, “ON” 
(P*213, 223, 233, 243, 253, 263) and “OFF” 
(P*214, 224, 234, 244, 254, 264).