Page 42
The default values used for determining the relay setpoints, when setting
Alarm and Control relays, via the Quick Setup menu are entered as a % of
span and are as follows.
Application
Number of
Cntl Relays
Cntl Relay
Number
On
Setpoint
Off
Setpoint
Cntl. Down
One
Control 1
80%
20%
Cntl. Down
Two
Control 1
Control 2
80%
70%
20%
20%
Cntl. Down
Three
Control 1
Control 2
Control 3
80%
70%
60%
20%
20%
20%
Cntl. Down
Four
Control 1
Control 2
Control 3
Control 4
80%
70%
60%
50%
20%
20%
20%
20%
Cntl. Down
Five
Control 1
Control 2
Control 3
Control 4
Control 5
80%
70%
60%
50%
40%
20%
20%
20%
20%
20%
Cntl. Down
Six
Control 1
Control 2
Control 3
Control 4
Control 5
Control 6
80%
70%
60%
50%
40%
30%
20%
20%
20%
20%
20%
20%