EasyManua.ls Logo

Pulsar ULTRA TWIN - Page 50

Pulsar ULTRA TWIN
225 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 42
The default values used for determining the relay setpoints, when setting
Alarm and Control relays, via the Quick Setup menu are entered as a % of
span and are as follows.
Application
Number of
Cntl Relays
Cntl Relay
Number
On
Setpoint
Off
Setpoint
Cntl. Down
One
Control 1
80%
20%
Cntl. Down
Two
Control 1
Control 2
80%
70%
20%
20%
Cntl. Down
Three
Control 1
Control 2
Control 3
80%
70%
60%
20%
20%
20%
Cntl. Down
Four
Control 1
Control 2
Control 3
Control 4
80%
70%
60%
50%
20%
20%
20%
20%
Cntl. Down
Five
Control 1
Control 2
Control 3
Control 4
Control 5
80%
70%
60%
50%
40%
20%
20%
20%
20%
20%
Cntl. Down
Six
Control 1
Control 2
Control 3
Control 4
Control 5
Control 6
80%
70%
60%
50%
40%
30%
20%
20%
20%
20%
20%
20%

Table of Contents

Other manuals for Pulsar ULTRA TWIN

Related product manuals