Page 43
Application
Number of
Cntl Relays
Cntl Relay
Number
On
Setpoint
Off
Setpoint
Cntl. Up
One
Control 1
20%
80%
Cntl. Up
Two
Control 1
Control 2
20%
30%
80%
80%
Cntl. Up
Three
Control 1
Control 2
Control 3
20%
30%
40%
80%
80%
80%
Cntl. Up
Four
Control 1
Control 2
Control 3
Control 4
20%
30%
40%
50%
80%
80%
80%
80%
Cntl. Up
Five
Control 1
Control 2
Control 3
Control 4
Control 5
20%
30%
40%
50%
60%
80%
80%
80%
80%
80%
Cntl. Up
Six
Control 1
Control 2
Control 3
Control 4
Control 5
Control 6
20%
30%
40%
50%
60%
70%
80%
80%
80%
80%
80%
80%
Relay
Function
Relay I.D.
On
Setpoint
Off
Setpoint
Alarm
HiHi
90%
85%
Alarm
High
85%
80%
Alarm
Low
10%
15%
Alarm
LoLo
5%
10%
Note
When using the Quick Setup Menu relays will be allocated to the
point of measurement you are currently setting up and the
availability of relays will depend on the number of relays used when
setting up the previous point of measurement via the Quick Setup
Menu for that point.

Table of Contents