146
NO.
Parameter
Name
Setting Range default
WRT
User
setting
f401
Electronic-
thermal
protection
characteristic
selection
6
Trip enable
stall
enable (forced
cooling motor)
7
Trip disable
stall
disable (forced
cooling motor)
2
f402
Motor 150%-
overload time
limit
10-2400 s 300
f403
Emergency stop
selection
0: Coast stop
1: Slowdown stop
2: Emergency DC
braking
0
f404
emergency
braking time
0.0-20.0 s 1.0
f405
Input phase
failure detection
0: Disabled, No tripping.
1: Enabled
0
f406
Output phase
failure detection
mode selection
0: Disabled
1: At start-up (Only one
time after power is
turned on)
2: At start-up (each
time)
3: During operation
4: At start-up + during
operation
5: Detection of cutoff on
output side
0
f407
Small current
trip/alarm
selection
0
Alarm
1
trip
0
f408
Small current
detection current
0~100% 0.00