148
NO.
Parameter
Name
Setting Range default
WRT
User
setting
f420
Detection of
output short-
circuit during
start-up
0: Each time (standard
pulse)
1: Only one time after
power is turned on
(standard pulse)
2: Each time (short-time
pulse)
3: Only one time after
power is turned on
(short-time pulse)
0
f421
Motor electric-
thermal
protection
retention
selection
0: disabled.
1: Enabled.
0
f422 AI1 input loss 1~100% 0
f423
Activation of the
inverter during
4-20mA signal
loss
0: No measures.
1: Coast stop.
2: switch to Fallback
speed.
3: Speed maintaining.
4: Slowdown stop.
0
f424 Fallback speed 0.0 Hz ~f007 0.0
f425
PTC thermal
selection
0: Disabled
1: Enabled (trip mode)
2: Enabled (alarm
mode)
0
f426
Resistor value
for PTC
detection
100-9999Ω 3000
f428
Cumulative
operation time
alarm setting
0.0-999.9 h (0.1=10h) 610.0
f429
Inverter trip
retention
selection
0
clearing
1
maintaining
0

Table of Contents