Chapter 3: Using the Web Interface
293
Field
Data entered
Wait time after successful ping 5
To make the BCM2 declare the inaccessibility of the monitored
PDU when that PDU becomes inaccessible for around 12
seconds (4 seconds * 3 pings), enter the following data.
Field
Data entered
Wait time after unsuccessful ping 4
Number of consecutive unsuccessful pings for
failure
3
To make the BCM2 stop pinging the target PDU for 60 seconds (1
minute) after the PDU inaccessibility is declared. After 60
seconds, the BCM2 will re-ping the target PDU, enter the
following data.
Field
Data entered
Wait time before resuming pinging after
failure
60
The "Number of consecutive failures before disabling feature (0 =
unlimited)" can be set to any value you want.
5. Click Create.
Step 2: Create an event rule to send SNMP notifications for the
target PDU
1. Choose Device Settings > Event Rules.
2. Click .
3. Select the Enabled checkbox to enable this new rule.
4. Configure the following.
Field/setting
Data specified
Rule name Send SNMP notifications for PDU
(192.168.84.95) inaccessibility
Event Choose Server Monitoring >
192.168.84.95 > Unreachable
Trigger condition Select the Unreachable radio button
This will make the BCM2 react only when the target PDU becomes
inaccessible.

Table of Contents

Other manuals for Raritan PM Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Raritan PM Series and is the answer not in the manual?

Raritan PM Series Specifications

General IconGeneral
BrandRaritan
ModelPM Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals