Chapter 5: Using the Command Line Interface
sensor inlet 1 current upperWarning 20 lowerWarning 12
Results:
• The Upper Warning threshold for the inlet 1 RMS current is set to
20A. It also enables the upper warning threshold if this threshold has
not been enabled yet.
• The Lower Warning threshold for the inlet 1 RMS current is set to
12A. It also enables the lower warning threshold if this threshold has
not been enabled yet.
Example 3 - Upper Thresholds for Overcurrent Protector Sensors
The following command sets both the Upper Critical and Upper Warning
thresholds for the 2nd overcurrent protector.
sensor ocp 2 current upperWarning enable upperCritical 16
Results:
• The Upper Critical threshold for the 2nd overcurrent protector's
RMS current is set to 16A. It also enables the upper critical threshold
if this threshold has not been enabled yet.
• The Upper Warning threshold for the 2nd overcurrent protector's
RMS current is enabled.