Chapter 5: Using the Command Line Interface
490
<succ_ping> is the number of successful pings for declaring the
monitored device "Reachable." Valid range is 0 to 200.
<fail_ping> is the number of consecutive unsuccessful pings for
declaring the monitored device "Unreachable." Valid range is 1 to
100.
<succ_wait> is the wait time to send the next ping after a successful
ping. Valid range is 5 to 600 (seconds).
<fail_wait> is the wait time to send the next ping after a unsuccessful
ping. Valid range is 3 to 600 (seconds).
<resume> is the wait time before the BCM2 resumes pinging after
declaring the monitored device "Unreachable." Valid range is 5 to
120 (seconds).
<disable_count> is the number of consecutive "Unreachable"
declarations before the BCM2 disables the ping monitoring feature
for the monitored device and returns to the "Waiting for reliable
connection" state. Valid range is 1 to 100 or
unlimited
.
Deleting a Monitored Device
This command removes a monitored IT device from the server
reachability list.
config:# serverReachability delete <n>
Variables:
<n> is a number representing the sequence of the IT device in the
monitored server list.
You can find each IT device's sequence number using the CLI
command of show serverReachability as illustrated below.
Modifying a Monitored Device's Settings
The command to modify a monitored IT device's settings begins with
serverReachability modify
.
You can modify various settings for a monitored device at a time. See
Multi-Command Syntax
(on page 504).
Modify a device's IP address or host name:

Table of Contents

Other manuals for Raritan PM Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Raritan PM Series and is the answer not in the manual?

Raritan PM Series Specifications

General IconGeneral
BrandRaritan
ModelPM Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals