8. PARAMETER DESCRIPTION
IMR02C15-E4
8-18
Setting change rate limiter (up)
Setting change rate limiter (down)
Factory default setting:
The screen is not displayed.
Set the values for Setting change rate limiter up and down.
Data range Factory set value
1 (0.1) to Input span (Unit °C [°F])/unit time
0: Unused
[Factory set value of unit time: 0 (minute)]
0 (0.0)
Setting change rate limiter is not displayed as the default when the block
selection at F03 [S.F03] (P. 8-67) is set to “1: No display” in the
Engineering mode. To show the parameter, set the value to “0: Display.”
Set the unit time at Setting change rate limiter unit time (SVRT) at F70
(P. 8-136) in the Engineering mode.
Related parameters
Engineering mode:
• Setting change rate limiter (up), Setting change rate limiter (down) (P. 8-66)
• Setting change rate limiter unit time (P. 8-136)
Continued on the next page.
SVRU
SVRD