8. PARAMETER DESCRIPTION
IMR02C15-E4
8-17
Repeat execution times
Factory default setting:
The screen is not displayed.
Set Repeat execution times to repeat the ramp/soak control using Timer function
3 or 4.
Data range Factory set value
0 to 9999 (9999: Infinite times) 0
Timer function 3 or 4 should be selected to ramp/soak control.
Repeat execution times is not displayed as the default in the block
selection at F02 [S.F02] (P. 8-65) is set to “1: No display” in the
Engineering mode. To show the parameter, set the value to “0: Display.”
For the process of ramp/soak control with Repeat execution times, refer to
Ramp/Soak control (Timer function 3, Timer function 4) (P. 7-9).
Related parameters
Parameter setting mode:
• Timer 1, Timer 2, Timer 3, Timer 4 (P. 8-15)
• Timer function (P. 8-16)
Engineering mode:
• Repeat execution times (P. 8-64)
RPTS