8. PARAMETER DESCRIPTION
8-24 IMR02C15-E4
Autotuning (AT)
Factory default setting:
The screen is displayed.
To set Autotuning (AT), set the value to “1.” This allows automated calculating
of proportional, integral and derivation.
Data range Factory set value
0: PID control
1: Autotuning (AT)
0
Autotuning (AT) is not displayed when the block selection at F05 [S.F05]
(P. 8-72) is set to “1: No display” in the Engineering mode.
For starting method and conditions for Autotuning (AT),
refer to 6.2 Autotuning (AT) (P. 6-8).
Related parameters
Engineering mode:
Autotuning (AT) (P. 8-71)
AT cycles (P. 8-130)
AT differential gap time (P. 8-131)
ATU